Shock protection boundaries are distances set in NFPA 70E, the limited and restricted approach boundaries, that control how close people may come to exposed energized electrical parts based on their training and protection.

Shock protection boundaries are approach distances around exposed energized electrical conductors or circuit parts. They control who may come close to live parts and what protection they need. NFPA 70E defines two shock boundaries: the limited approach boundary and the restricted approach boundary. A separate arc flash boundary addresses burn hazards from an arc flash.
The boundaries exist because electric shock can happen without touching a conductor. At higher voltages, current can arc across air gaps, and a tool, ladder or body part can slip into contact in an instant.
Many electrical injuries happen to people who were not working on the equipment at all, such as a helper, painter or passerby who stepped too close to an open panel. Boundaries give everyone a clear, physical line that marks where the danger starts and who is allowed inside.
They also guide PPE and planning. Knowing the boundaries for each piece of equipment tells qualified workers when they need rubber insulating gloves, insulated tools and a documented plan, and when an energized work permit may be required.
The limited approach boundary is the distance from an exposed live part within which a shock hazard exists. Unqualified persons may not cross it unless they are continuously escorted and advised by a qualified person. It is set further out for movable conductors, such as overhead lines that can swing, than for fixed circuit parts.
The restricted approach boundary is the closer distance within which there is an increased likelihood of shock from arc-over or accidental movement. Only qualified persons may cross it, and they must have an approved plan, use shock-protective PPE such as rubber insulating gloves, and position themselves to keep body parts out of the boundary as much as possible.
NFPA 70E gives boundary distances in tables by voltage. Common examples for alternating current systems include:
An electrician opened a 480-volt motor control center to take voltage readings. A painter working nearby walked over to watch and leaned within a foot of the open bucket. The electrician stopped work, but the near miss showed there was no barrier to keep unqualified workers back.
The facility began barricading the limited approach boundary, 3 feet 6 inches around open equipment, before any panel was opened, assigned an attendant for longer tasks and added boundary awareness to annual training for all trades.
It is the distance from an exposed energized part within which a shock hazard exists. Unqualified persons may not cross it unless escorted by a qualified person.
It is the closer distance where there is an increased risk of shock. Only qualified persons with proper PPE and a plan may cross it.
It was removed from NFPA 70E in the 2015 edition. The limited and restricted approach boundaries remain.
No. The arc flash boundary is based on burn risk from an arc flash, not shock. It can be larger or smaller than the shock boundaries, so both must be considered.
Under the NFPA 70E AC table, for 151 to 750 volts the limited approach boundary is 3 feet 6 inches for fixed circuit parts and 10 feet for exposed movable conductors. The restricted approach boundary is 1 foot.
A qualified person has the skills and knowledge related to the equipment and has received safety training to identify and avoid the electrical hazards involved, as defined by OSHA and NFPA 70E.