Fire Watch is a trained person assigned to look for fire and raise the alarm during and after hot work, or while sprinklers, alarms or other fire protection systems are out of service.

A fire watch is a trained person, or team, assigned to look for fire in a defined area and act on it immediately, either because work in that area could start a fire or because the building's normal fire protection is not working. Their whole job is to see a fire early, raise the alarm and, where safe, put it out while it is still small.
The term covers two situations that share a name but have different triggers. A hot work fire watch stands beside welding, cutting, grinding or torch-applied roofing and stays on after the work stops, because smoldering material can flare up long after the sparks end. An impairment fire watch patrols a building when sprinklers, fire alarms or other systems are out of service, filling in for the detection and suppression that would normally be there. Both are temporary controls. Neither one is a substitute for fixing the underlying hazard or getting the system back in service.
In general industry, OSHA 29 CFR 1910.252(a)(2)(iii) requires fire watchers whenever welding or cutting happens where more than a minor fire might develop. The listed conditions include appreciable combustibles within 35 feet of the work, more distant combustibles that sparks could easily reach, wall or floor openings within 35 feet that expose combustibles in adjacent areas, and combustibles on the other side of metal walls, ceilings or roofs that could ignite by conduction or radiation. The fire watch must be maintained for at least half an hour after welding or cutting ends.
In construction, 29 CFR 1926.352(e) requires additional personnel to guard against fire during the work and for a sufficient period afterward to make sure no possibility of fire exists. It does not give a fixed time.
NFPA 51B, the consensus standard for hot work, is stricter. Since the 2019 edition it has called for a fire watch of at least one hour after hot work is complete, followed by fire monitoring of the area for up to three additional hours, as decided by the person who authorized the permit. Many insurers and corporate standards adopt the NFPA 51B times rather than OSHA's 30 minutes.
When fire protection systems are impaired, fire codes rather than OSHA usually drive the requirement. NFPA 25 sets out an impairment program for water-based systems, with an impairment coordinator, tagging, notifications and measures such as a fire watch. Building and fire codes, including NFPA 101, NFPA 1 and the International Fire Code, commonly require a fire watch or evacuation when a fire alarm is out of service more than 4 hours, or a sprinkler system more than 10 hours, in a 24-hour period. The editions adopted and local amendments vary, and the local fire official often sets the specific terms.
A fire watch is a dedicated role. The person should not be welding, running material or doing anything that takes their eyes off the area. Typical duties include:
At minimum, a suitable extinguisher or charged hose, a reliable way to raise the alarm (radio, phone or manual pull station location), a flashlight and the log. For hot work, 1910.252 requires that fire watchers have extinguishing equipment readily available and be trained in its use; the right extinguisher depends on the materials present, which ties back to fire extinguisher classes. Workers covering lone night patrols during impairments need a check-in arrangement, such as mobile worker monitoring, since they are often the only person in a large building.
The most common failure is the fire watch walking away when the welder does. Smoldering fires in insulation, wall cavities, roof decks and dust deposits can take hours to show visible flame. This is why NFPA 51B extended its post-work times.
The welder's helper is often named as the fire watch while also handing tools and holding parts. Divided attention defeats the point.
Heat travels through metal decks, ducts and pipes. A fire can start in a room nobody is looking at. Good fire watches open the adjacent room or climb to the floor above.
Patrols that are not recorded are hard to defend in an audit or after a loss. Insurers and fire officials will ask for the log.
A food manufacturing plant scheduled overnight welding to modify a support bracket on a spiral freezer. The permit-to-work listed a fire watch, and the maintenance contractor's apprentice was assigned. He stayed for the required 30 minutes after work ended, logged "no fire" and left. About 90 minutes later, sparks that had fallen into polyurethane insulation behind a stainless panel started to smolder. Smoke detectors in the room alerted the control room, and the night shift isolated the area and called the fire department. Damage was limited, but the freezer line was down for two days.
The investigation found that the permit template used OSHA's 30 minutes, the panel had not been opened during the pre-work inspection, and nobody had checked the insulated cavity. The plant updated its permit to NFPA 51B times, with one hour of fire watch and up to three hours of monitoring, required a thermal camera check of insulated panels before signing off, and added hot work in insulated enclosures to its job hazard analysis library.
Generally no. The person doing hot work is focused on the weld, often wearing a dark lens that limits their view of the surroundings. OSHA and NFPA 51B both treat the fire watch as a separate assignment. For very small, low-risk jobs, the permit authorizer may decide a fire watch is not required at all, but that is different from letting the operator do both.
OSHA requires that fire watchers be trained in using the extinguishing equipment and know how to sound the alarm. There is no federal license. Some cities, notably New York, require a certificate of fitness for certain fire watch roles. Employers should train fire watches on site alarms, extinguisher use, patrol routes, logging and when to evacuate rather than fight a fire.
Many fire officials expect every affected area to be checked at least once an hour, with the route and times recorded. Some higher-risk occupancies, such as hospitals or buildings with sleeping occupants, may need more frequent patrols or a person stationed on each floor. Confirm with the local fire official, since they usually set the terms of an impairment fire watch.
For hot work, the permit authorizer signs off after the required watch and monitoring periods, once the area is confirmed free of fire. For impairments, the fire watch ends when the system is restored, tested and confirmed in service, and anyone notified at the start, such as the fire department, alarm company or insurer, has been told it is back.
Part of SafetyIQ's EHS glossary: plain-English definitions of workplace health and safety terms.